    JHZX-GP20 type, transformer oil spectrum online monitoring device
    • JHZX-GP20 type, transformer oil spectrum online monitoring device

    JHZX-GP20 type, transformer oil spectrum online monitoring device

    ??? 
    recommendation index:
    Automatic quantitative cycle cleaning, oil intake, oil and gas separation, sample analysis
    Data processing, real-time alarm
    Negative pressure-constant temperature-dynamic headspace degassing technology
    Direct sampling of oil intake port, full cycle oil circuit design
    • Using TDLAS detection principle combined with negative pressure-constant temperature-dynamic headspace degassing technology, the minimum detection value of C2H2 is less than or equal to 0.2 μL/L, which meets the national grid enterprise standard Q/GDW10563-2021 750kV and above voltage class A standard

    • It can realize automatic quantitative cycle cleaning, oil intake, oil and gas separation, sample analysis, data processing, and real-time alarm

    • Rapid on-line monitoring of dissolved fault gas content and growth rate in oil of oil-immersed power high voltage equipment such as transformers

    • Early prediction of equipment failure hazard information through fault diagnosis expert system to avoid equipment accidents, reduce major losses, and improve the reliability of equipment operation

    name

    component

    parameter

    minimum detectable quantity

    C2H2

    0.2μL/L

    CH4、C2H6、C2H4

    0.5μL/L

    H2

    2μL/L

    CO、CO2

    10μL/L

    precision

    C2H2

    detection value ≤ 5 μL/L, ≤ ± 0.2 μL/L or ± 30% (whichever is larger)

    When the detection value is 5 μL/L~ 10 μL/L, ≤ ± 30%

    detection value ≥ 10μL/L, ≤ ± 20%

    H2

    detection value ≤ 20 μL/L, ≤ ± 2 μL/L or ± 30% (whichever is larger)

    detection value  ≥ 20μL/L, ≤ ± 30%

    CH4、C2H6、C2H4

    detection value≤ 10 μL/L, ≤ ± 0.5 μL/L or ± 30% (whichever is larger)

    detection value ≥ 10μL/L, ≤ ± 30%

    CO、CO2

    detection value≤ 100 μL/L, ≤ ± 25 μL/L or ± 30% (whichever is larger)

    detection value ≥ 100μL/L, ≤ ± 30%

    repeatability

    RSD support

    ≤2%

    range

    H2

    0.5 ± 5000μL / L repeated

    CO、C02

    0 ° C ± 20000μL / L

    CH4、C2H6、C2H4

    0.5 ± 5000μL / L repeated


    Related recommendations

    JHZF-1000 GIS Electrical Equipment SF6 Gas Integrated Online Monitoring System

    Equipped with SF6 equipment internal gas component detection function and display function

    JHZX-SP10 Transformer chromatography online monitoring device

    With 7 components of dissolved gas in oil and micro-water monitoring function